ARC700 Paperless Recorder

ALIAPANEL ARC700 Series Paperless Recorder used the most Advanced technology, to be aimed to various industry application,and designed a small sized and lower power consumed, high accuracy, common use, it can also overcome the older big sized recorder, not easy installation…etc defects.

FEATURES

Small sized(72mm*72mm), 128*64Pixels, Blue Screen 8MB memory installed inside, applied to long terms data record Common input signal, mA, VDC, T/C, RTD…etc signal High Accuracy +/-0.15% of Reading Maximum to 2 points Relay or 1 point 4-20mA output and 1 points 24VDC output Maximum can receive 4 channels input signal Could selected 24VDC Aux. Power supply for 2 wires system It can Display / Record single point, Multi-point, Trend, Bargraph The recorded data could be stored in USB memory, and take out to computer make soft analysis

SPECIFICATION

Number of Inputs:Display:

1, 2, 3, 4 Channels2-Inch Blue Screen LCD(128 * 64 Pixels)

Inputs:Trend & Bargraph

T/C (K, S, B, E, J, N, T)Horizontal

RTD( PT100 W ),CU50, CU100Digital

DCA(4-20 mA, 0-10 mA)4-1/2 digits programmable

DCV( 0-5V, 1-5V)Engineer unit

Accuracy:52 Engineering units

+/-0.15% of SpanParameter Protect

Response Time:Password entry

80 msData saving Period:

Alarm Function:1 Second to 3600 Seconds

Up to four points per channelRecording Capability:

Alarm Types:144 Hours(4 Points, 1 Data/Second)

High and Low Limits, High-High,376 Years(1 Point, 1 Data/Hour)

Low-LowPassword Protection:

Output:6 Digits

4-20 mA, 1 pointPC software:

Relay, 1A/600V, SPDT, up to 2 pointsCompatible with Windows 2000/XP/Vista

Aux. Power supply:Display

24VDC, 85 mA max. for TransmitterTrend, Digital, Circular, Alarm, Bargraph

Storage Memory:Convert function

16MB(on board)can be save as excel files

Recycling Mode:Enclosure:

Newest Data over-writes to oldest dataNEMA 3 / IP 54

Recording Data Shift:Weight:

USB memory(2GB)0.4 Kg maximum

Display update Rate:Dimensions:

1 Second72 mm * 72 mm (H) * 100 mm (D)

Keyboard:Ambient Temperature:

4 Keys (SET, Shift , UP, Down) for -10 to +55 oC

programming and display controlAmbient Humidity:

Parameter Storage:10% to 85%RH (at 5 to 40 oC)

Operation Parameters are stored by Power Supply:

EEPROM for more then 10 years90-260VAC, 50/60Hz

Power Consumption:

5 W

Communication:

RS 485 (MODBUS Protocol)

Related Posts