Electromagnetic Flow Converter
SPECIFICATION
Excitation:Keyboard:
Square wave4 keys from external for programming
Display:and display control.
4 lines LCD with back lightLow Flow Cutoff:
Line 10 to 9.9 %
Date and TimeDatalogger Function:
Line 299 times records for power on/off
6 digit flowrateRecord Data:
7 digit energy value Date/Time when Power on/off
Fault code 99 years flow rate / energy /
Supply temperatureTemperature / Total flow / Total energy
Line 3One Record Data per Hour
9 digit totalizer for forward / reverse flowDamping:
9 digit totalizer for heat / cold energy0.1 to 99.9 Second
Fault code contentSelf Diagnosis:
Return temperatureThe following error message is
Line 4indicated during application
Differential temperature– Coil fail
Unit– Power fail
L/S , L/M , L/H , M3/S , M3/L , M3/H– Output overanged
KW , MW , KJ/H , MJ/H , GJ/H – Internal error
Measuring Range:– Overflow
Min. 0 to 0.15 m/s– Empty pipe
Max. 0 to 15 m/sCable Entry:
Accuracy:PG11
+/-0.4% of reading (Velocity >= 0.5 m/s)Protection Class:
+/-0.002 m/s (Velocity < 0.5 m/s)IP 65
Repeatability:Ambient Temperature:
+/-0.1% of reading
-25 to +65 oC
Current Output:Material:
4-20 mA (Isolated)Aluminum Alloy
LoadTemperature Input:
Max. 600 PT1000, 2 wire
Pulse output:Power Supply:
Open collector90-260 VAC, 50/60 Hz
Rating24 VDC +/- 10% (Option)
3 to 30 VDC, 20 mA Max. Power Consumption:
Pulse Rate:3-17 W (depending on the sensor size)
1)Scale pulse, (Pusle/M3, Pulse/L, Other)Weight:
2)Frequency, 0-5000 Hz1.4 Kg
Communication:Mounting:
RS 485(MODBUS Protocol)Wall mounting
HART signalBracket on 2″ pipe
Data Storage:
Operation parameters and totalization
figures are stored by EEPROM for more
than 10 years